4.1. Internal Memory BatReg2

ID

Field

Type

Privileges

Description

0

Firmware ID

string

R-only

Firmware ID

1

Model

string

R-only

Model name

2

Serial Number

string

R-only

Serial Number

3

MAC Address

string

R-only

MAC Address of Ethernet

6

Hardware revision

string

R-only

Hardware revision

7

Capabilities

string

R-only

Available capabilities

8

Brand

string

R-only

Device brand

10

Module ID

string

Admin

Default value is the module s/n

12

Error Code Description

int [0|1]

Admin

Adds error description after #NAK when enabled (1)

13

Allow Remote OFF Cmd

int [0|1]

Admin

It’s possible OFF the device when it’s in Local Mode

15

TFT timeout

int

Admin

LCD timeout [minutes]

30

Current Slew Rate

float

User

Slew rate used in CC Mode [A/s]

31

Voltage Slew Rate

float

User

Slew rate used in CV Mode [V/s]

40

PID Max Voltage

float

Admin

PID Max Voltage [V]

41

PID Min Voltage

float

Admin

PID Min Voltage [V]

42

PID Max Current

float

Admin

PID Max Current [A]

43

PID Min Current

float

Admin

PID Min Current [A]

50

PID Kp_v

float

Admin

Kp parameter of Voltage PID

51

PID Ki_v

float

Admin

Ki parameter of Voltage PID

52

PID Kd_v

float

Admin

Kd parameter of Voltage PID

53

PID Kp_i

float

Admin

Kp parameter of Current PID

54

PID Ki_i

float

Admin

Ki parameter of Current PID

55

PID Kd_i

float

Admin

Kd parameter of Current PID

100

Output Over-Current Limit

float

Admin

Output over-current threshold [A]

101

Output Over-Voltage Limit

float

Admin

Output over-voltage threshold [V]

110

Max PS Temperature

float

R-only

Max Power Stage Temperature threshold [°Celsius]

112

Min TC Temperature

float

Admin

Min Thermocouple Temperature [°Celsius]

113

Max TC Temperature

float

Admin

Max Thermocouple Temperature [°Celsius]

114

TC Temperature Check Enable

int

Admin

Enable Thermocouple Temperature Check (1)

140

Interlock Enable Mask

hex

Admin

Interlocks enable mask

141

Interlock Activation Level Mask

hex

Admin

Interlocks polarity mask

142

Interlock Hard Fault Mask

hex

Admin

Interlocks direct mask

144

Interlock #1 Intervention Time

int

Admin

Interlock #1 intervention time [ms]

145

Interlock #1 Name

string

Admin

Interlock #1 name

146

Interlock #2 Intervention Time

int

Admin

Interlock #2 intervention time [ms]

147

Interlock #2 Name

string

Admin

Interlock #2 name

148

Interlock #3 Intervention Time

int

Admin

Interlock #3 intervention time [ms]

149

Interlock #3 Name

string

Admin

Interlock #3 name

150

Interlock #4 Intervention Time

int

Admin

Interlock #4 intervention time [ms]

151

Interlock #4 Name

string

Admin

Interlock #4 name

180

Calibration Date

string

R-only

Calibration date

181

Current Calib. Param. a

float

R-only

Current cubic calib. param. a

182

Current Calib. Param. b

float

R-only

Current cubic calib. param. b

183

Current Calib. Param. c

float

R-only

Current cubic calib. param. c

184

Current Calib. Param. d

float

R-only

Current cubic calib. param. d

185

Voltage Calib. Param. a

float

R-only

Voltage cubic calib. param. a

186

Voltage Calib. Param. b

float

R-only

Voltage cubic calib. param. b

187

Voltage Calib. Param. c

float

R-only

Voltage cubic calib. param. c

188

Voltage Calib. Param. d

float

R-only

Voltage cubic calib. param. d

191

Analog Input Calib. Param. a

float

R-only

Analog Input linear calib. param. a

192

Analog Input Calib. Param. b

float

R-only

Analog Input linear calib. param. b

193

Aux Input Calib. Param. a

float

R-only

Aux. Input linear calib. param. a

194

Aux Input Calib. Param. b

float

R-only

Aux. Input linear calib. param. b

210

Reserved

-

R-only

-

211

Reserved

-

R-only

-

212

Reserved

-

R-only

-

214

Reserved

-

R-only

-

215

Reserved

-

R-only

-

221

Acoustic Alarm Enable

int

Admin

Enable Acoustic Alarm (1)

225

DC-Link Voltage

float

R-only

DC-Link Voltage [V]