6.1. Status Register

The Status Register indicates the unit’s status. To read it, see the REG Command.

Bit(s)

Field

Description

Note

[1:0]

Module status

00: OFF

see OUT Command

01: ON

11: Wait for On

[2]

Fault bit

Fault state

see Fault Register

[3]

Reserved

-

[4]

Loop mode

0: CC

see LOOP Command

1: CV

[6:5]

Reserved

-

[7]

PID Limitation bit

PID is in saturation

The device output current/voltage is limited

[9:8]

Update mode

00: Normal

see UPMODE Command

10: Waveform

[11:10]

Reserved

-

[12]

Local mode [1]

0: Remote

Local display commands are rejected

1: Local

Only local display commands are accepted

[15:13]

Reserved

-

[18:16]

Trigger mode

000: Trigger disabled

see TRIGGER Command

001: Pos. Edge

010: Neg. Edge

011: Both Edges

100: High Level

101: Low Level

[20:19]

Reserved

-

[21]

Ramping

A ramp is performing

[23]

Reserved

-

[24]

Waveform execution

A waveform is performing

[26:25]

Waveform mode

00: Start

see WAVE Command

01: Point

10: Gate

11: Gate reset

[27]

Reserved

-

[31:28]

Reserved

-

See also

Please see the User’s Manual for more details.